PCI-1724U User Manual 50
Step 2: Select the output range of the channel to 0~20mA or 4~20mA.
Step 3: Click the Calibration button to start the calibration process. The
Calibration Wizard window will pop up.
Figure D.9: Click the Calibration Button to Launch the Calibration
Step 4: Follow the instruction of Calibration Wizard and click the Next
button to proceed to the next step.
Fig.3 The start-up window of offset calibration
Step 5: At this step, the Wizard will output 4 mA on the channel you
selected. Please check the value on the meter is in the range (I). If the
value does not fit, please perform the adjustment.
There are 3 ways to perform the adjustment.
1. Move the slider (II).
2. Input the adjust value (III). Note that only if the [Set] button is pressed,
the value will take effect.
Note Each calibration process can calibrate only one chan-
nel and one input range at a time.
Comments to this Manuals